Fire Alarm Panels (Gamewell-FCI) – Alert Failure Risk (2016)
Check Your Product
According to the U.S. Consumer Product Safety Commission (CPSC)
Product
Gamewell-FCI fire alarm panels (ILI-MB-E3 and ILI-S-E3)
Lot Codes / Batch Numbers
Not specified in CPSC notice. Check official source for details.
Product Images
Source: U.S. Consumer Product Safety Commission
A manufacturer is recalling Gamewell-FCI fire alarm panels (ILI-MB-E3 and ILI-S-E3). The hazard is: When configured in a certain way, the panels can become non-responsive and connected detectors in th. Based on CPSC recall notice.
Summary derived from CPSC notice
The following details were not provided by CPSC: UPC codes.
Reason for Recall
As stated by CPSC
This recall is for the ILI-MB-E3 and ILI-S-E3 Gamewell-FCI fire alarm panels in commercial buildings. This issue is limited to a specific configuration of Signaling Line Circuit (SLC) devices. To occur, the SLC must include at least two of the following detectors in any combination: Acclimate, 4-Warn, Photo/CO and iFAAST. The issue would occur only if the detectors are addressed within the same FlashScan polling group. Detectors installed in a different combination are not affected.
Reported concern (CPSC)
When configured in a certain way, the panels can become non-responsive and connected detectors in the area can fail to detect and respond to an alarm.
Recommended Action
Per CPSC guidance
Consumers should immediately contact the distributor to obtain the free repair, a firmware upgrade.
Verify this information on the official source
For complete details and official instructions, check the U.S. Consumer Product Safety Commission (CPSC) directly.
View official CPSC recall noticePage updated: Jan 6, 2026