Greenheck Ventilation Units – Mechanical Defect (2005)
Check Your Product
According to the U.S. Consumer Product Safety Commission (CPSC)
Product
Greenheck Sidewall, Rooftop and Centrifugal Inline Ventilation Units
Lot Codes / Batch Numbers
Not specified in CPSC notice. Check official source for details.
Product Images
Source: U.S. Consumer Product Safety Commission
A manufacturer is recalling Greenheck Sidewall, Rooftop and Centrifugal Inline Ventilation Units. The hazard is: LUX 3/8-inch spinlock bolts supplied with these units may not have been properly heat treated, which. Based on CPSC recall notice.
Summary derived from CPSC notice
The following details were not provided by CPSC: UPC codes.
Reason for Recall
As stated by CPSC
Affected units are Sidewall, Rooftop and Centrifugal Inline ventilation units built between August 11, 2004 and April 29, 2005, containing 16-thread-per-inch 3/8-inch by ¾-inch spinlock bolts with LUX head markings. Affected model numbers are RBU, RBUMO, RDU, RB/R, SB/S, and BSU 360-420 with serial numbers 04HXXXXX through 05DXXXXX. The model and serial numbers are found on metal identification plate on the units.
Reported concern (CPSC)
LUX 3/8-inch spinlock bolts supplied with these units may not have been properly heat treated, which can result in the bolts breaking. Bolt failure during lifting for rooftop installation or after installation could cause the unit or components to fall and injure bystanders.
Recommended Action
Per CPSC guidance
LUX spinlock bolts in affected units will be replaced at no cost to the end user.
Verify this information on the official source
For complete details and official instructions, check the U.S. Consumer Product Safety Commission (CPSC) directly.